Minimum boiler supply temperature during a setpoint
demand.
10K 2 = DHW,
OR
DHW THRU = NONE
363 View Menu (1 of 1)
-31 to 266˚F
(-35 to 130˚C)
- - -, OFF, 70 to 220˚F
(OFF, 21 to 104˚C)
Current DHW tank temperature.
10K 2 = DHW
DHW THRU NONE
Section
LTD
USER
INST
ADV
C1
C4
Range
Access
Level
Description
Current outdoor air temperature as measured by the outdoor
sensor. This is the default display for the control.
-67 to 149˚F
(-55 to 65˚C)
Target room air temperature. “– –” denotes no heat is
required.
10K 1 = INDR
- - -, 35 to 100˚F
(2 to 38˚C)
D3
Measured room air temperature at the indoor sensor.
10K 1 = INDR
-58 to 167˚F
(-50 to 75˚C)
D3
This is the signal that is being received from a tekmar Zone
Control that is operating mixing zones.
10K 1 = MIX
- - -, 35 to 110˚F
(2 to 43˚C)
D3
This is the signal that is being received from a tekmar Zone
Control that is operating the boiler zones.
10K 1 = Boil
- - -, 35 to 110˚F
(2 to 43˚C)
B2
Current slab sensor temperature.
10K 1 = SLAB
MIX MIN = OFF
-58 to 167˚F
(-50 to 75˚C)
D3
Target mixed supply is the temperature the control is
currently trying to maintain at the mixing sensor.
- - -, 35 to 248˚F
(2 to 120˚C)
D1
Current mixed supply water temperature as measured by
the mixing sensor.
-31 to 266˚F
(-35 to 130˚C)
D1
Target boiler supply is the temperature the control is currently
trying to maintain at the boiler sensor +/- 1/2 of the
differential.
- - -, 35 to 248˚F
(2 to 120˚C)
B1
Current boiler supply water temperature as measured by
the boiler sensor.
-31 to 266˚F
(-35 to 130˚C)
Current storage tank temperature as measured by the
storage tank sensor.
10K 2 = STOR
-31 to 266˚F
(-35 to 130˚C)
E2
Minimum boiler supply temperature during a DHW demand.
10K 2 DHW
DHW THRU NONE
- - -, OFF, 100 to 220˚F
(OFF, 38 to 104˚C)
C1
Target DHW tank temperature.
10K 2 = DHW
DHW THRU NONE
- - -, OFF, 70 to 190˚F
(OFF, 21 to 88˚C)
C1
B1