Tekmar 162 Setpoint Control Installation Uživatelský manuál

Procházejte online nebo si stáhněte Uživatelský manuál pro Senzory Tekmar 162 Setpoint Control Installation. tekmar 162 Setpoint Control Installation User Manual Uživatelská příručka

  • Stažení
  • Přidat do mých příruček
  • Tisk
  • Strana
    / 32
  • Tabulka s obsahem
  • KNIHY
  • Hodnocené. / 5. Na základě hodnocení zákazníků
Zobrazit stránku 0
Information
Brochure
Choose controls
to match
application
1
Application
Brochure
Design your
mechanical
applications
2
Rough In
Wiring
Rough-in
wiring
instructions
3
Wiring
Brochure
Wiring and
installation of
specific control
4
Data
Brochure
Control settings
and sequence of
operation
5
Job
Record
Record settings &
wiring details for
future reference
6
D 162
08/07
tekmarNet
®
4 Setpoint Control 162
- Data Brochure
1 of 32 © 2007 D 162 - 08/07
Introduction
The Setpoint Control 162 is a single stage heat or cool setpoint control that can operate on an On / Off differential or can
operate on Pulse Width Modulation. The control includes a second relay contact to operate a system pump. The control
includes special modes for hot tub, indirect domestic hot water tank, radiant floor, and pool applications.
Features
tN4 Compatible
On / Off Differential
Pulse Width Modulation
System Pump
Hot Tub Operation
DHW Tank Operation
Floor Operation
Pool Operation
Exercising
Scenes
Temperature Sensor Input
Programmable Setback Scheduling
One Stage Heat or Cool
Zobrazit stránku 0
1 2 3 4 5 6 ... 31 32

Shrnutí obsahu

Strany 1 - - Data Brochure

Information BrochureChoose controlsto matchapplication1Application BrochureDesign your mechanical applications2Rough InWiringRough-inwiring instructio

Strany 2 - Display and DIP Switches

© 2007 D 162 - 08/07 10 of 32 ADJUST Menu (2 of 6)Mode Item Field Range Access Description2OFF, 40°F (4.5°C) to Hot Tub MaximumDefault = 95°F (35.0

Strany 3

11 of 32 © 2007 D 162 - 08/07Mode Item Field Range Access Description6 OFF, 40°F (4.5°C) to Pool MaximumDefault = 78°F (25.5°C)LTDUSErInSTADVSET

Strany 4 - User Interface

© 2007 D 162 - 08/07 12 of 32 ADJUST Menu (4 of 6)Mode Item Field Range Access Description1230 to 20:00 min in10 sec incrementsDefault = 0:30ADVMIN

Strany 5 - Application Overview

13 of 32 © 2007 D 162 - 08/07ADJUST Menu (5 of 6)Mode Item Field Range Access Description123456OFF, OnDefault = OnInSTADVRELAY 1 PUMP SECTION RS

Strany 6 - Mode 6 Pool

© 2007 D 162 - 08/07 14 of 32 ADJUST Menu (6 of 6)Mode Item Field Range Access Description12456NONE, ZONE, CTRLDefault = NONEADVWWSD SECTION RSelec

Strany 7 - Display Menus

15 of 32 © 2007 D 162 - 08/07Item Field RangeAccessDescriptionUSErInSTADVCURRENT TIME AND DAY SECTION KDisplays the current time and day of the

Strany 8

© 2007 D 162 - 08/07 16 of 32 Item Field RangeAccessDescriptionOcc, Away, PERM 1, PERM Away 2, PERM UnOcc 3, PERM 4, PERM 5, TMPY Occ 6, TMPY 7, TM

Strany 9

17 of 32 © 2007 D 162 - 08/07SCENE Menu (2 of 2) Note: The SCENE menu is not available when the Application Mode is set to Pool (6) SCENE MENUIt

Strany 10 - ADJUST MENU

© 2007 D 162 - 08/07 18 of 32 SCHD (Schedule) Menu (2 of 2) SCHEDULE MENU Item Field RangeAccessDescription– –:– – ,12:00 AM to 11:50 PMor– –:– –,0

Strany 11

19 of 32 © 2007 D 162 - 08/07Item Field RangeAccessDescriptionSEC, LTD, USEr,InST, ADVDefault = USErSECLTDUSErInSTADVACCESS LEVEL The access lev

Strany 12

© 2007 D 162 - 08/07 2 of 32 Table of ContentsDIP Switches Table of Contents ...2Display a

Strany 13

© 2007 D 162 - 08/07 20 of 32 Application Mode 1 - On / Off Setpoint SECTION AApplication Mode 1 is a generic setpoint control operation using an

Strany 14

21 of 32 © 2007 D 162 - 08/07Pressing the UP button while in the VIEW menu starts operation of the Hot Tub for the time set.To Stop operation pr

Strany 15 - TIME MENU

© 2007 D 162 - 08/07 22 of 32 Pressing the UP button while in the VIEW menu starts operation of the Hot Tub for the time set.To Stop operation pres

Strany 16 - SCENE MENU

23 of 32 © 2007 D 162 - 08/07Select the heating or cooling cycle length in minutes for Application Modes 4 (Setpoint), 5 (Floor), and 6 (Pool).

Strany 17 - SCHEDULE MENU

© 2007 D 162 - 08/07 24 of 32 Sensor Input SECTION JThe Setpoint Control 162 requires a temperature sensor (Universal Sensor 071 included) to be c

Strany 18

25 of 32 © 2007 D 162 - 08/074 Event 2 EventOccupied 1 OccupiedUnoccupied 1 UnoccupiedOccupied 2Unoccupied 2ScheduleModeEvent24hrSatSunMonTueWeT

Strany 19 - MISC MENU

© 2007 D 162 - 08/07 26 of 32 Away Hold SECTION NTo setback the temperature while the occupants are away, use the Permanent Away 2 scene. This sce

Strany 20 - Sequence of Operation

27 of 32 © 2007 D 162 - 08/07the occupied period. During the unoccupied periods, the exchange supply water temperature is lowered by the differe

Strany 21

© 2007 D 162 - 08/07 28 of 32 Outdoor TemperatureThe setpoint control can display the outdoor temperature in the View menu when connected to a tN4

Strany 22

29 of 32 © 2007 D 162 - 08/07Error MessagesLocal Errors and Device ErrorsError messages are used to indicate a problem somewhere in the system.

Strany 23 - Cycle Length SECTION G

3 of 32 © 2007 D 162 - 08/07DisplayAccess Levels The Access Level restricts the number of Menus, Items and Adjustments that can be accessed by t

Strany 24 - Time Clock SECTION K

© 2007 D 162 - 08/07 30 of 32 Error Messages (1 of 2) Error Message DescriptionADJUST ERRORThe setpoint control failed to read the ADJUST menu se

Strany 25 - Scenes SECTION M

31 of 32 © 2007 D 162 - 08/07Error Message DescriptionDEVICE LIMITThere are more than 24 devices on the tN4 bus. The additional devices must be

Strany 26 - Backlight SECTION Q

Limited Warranty The liability of tekmar under this war-ranty is limited. The Purchaser, by taking receipt of any tekmar product (“Product”), acknowle

Strany 27 - Priority

© 2007 D 162 - 08/07 4 of 32 Use the User Interface available on the Liquid Crystal Display (LCD) to setup and monitor the operation of the setpoin

Strany 28

5 of 32 © 2007 D 162 - 08/07LoadThe Setpoint Control 162 is designed to support six different applications. The items shown in the VIEW and ADJU

Strany 29 - Error Messages

© 2007 D 162 - 08/07 6 of 32 Applications: Pulse Width ModulationMode 4 Setpoint (PWM)LoadMode 5 FloorMode 6 PoolHeating PWM Operation Warmer Set H

Strany 30 - Error Messages (1 of 2)

7 of 32 © 2007 D 162 - 08/07VIEW MENUVIEW Menu (1 of 2)Mode Item Field Range Access Description12450:01 to 24:00 hrLTDUSErInSTADVOCCUPIED TIME

Strany 31 - Error Messages (2 of 2)

© 2007 D 162 - 08/07 8 of 32 VIEW MENUMode Item Field Range Access Description1OFF, -4°F (-20.0°C) to Setpoint Maximum (variable)USErInSTADVSET SET

Strany 32 - Cleaning the Control

9 of 32 © 2007 D 162 - 08/07ADJUST MENUADJUST Menu (1 of 6)Mode Item Field Range Access Description1234561, 2, 3, 4, 5, 6Default = 1InSTADVAPPLI

Komentáře k této Příručce

Žádné komentáře